What Size Wire for 30 Amps?

NEC Table 310.16 wire sizing for a 30-amp circuit — copper and aluminum, with the continuous-load and voltage-drop adjustments that change the answer.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · 75°C terminations
10 AWG

Ampacity 30A. Continuous loads (125%): 8.

Aluminum · 75°C terminations
8

Ampacity 40A. Continuous loads (125%): 8.

A 30A circuit is protected by a 30A breaker (NEC 240.6). The sizes above use the 75°C column of NEC Table 310.16.

Check your termination rating. Per NEC 110.14(C)(1), equipment rated 100A or less — or marked for 14 AWG through 1 AWG conductors — must be sized to the 60°C column unless its terminals are listed/marked for 75°C (most modern breakers are). When that applies the answer can be one size larger.

When the 30 Amp Answer Changes

Long runs (voltage drop)

Over distance, voltage drop can force a larger wire than ampacity alone. At 240V, 10 AWG copper drops about 1.5% at 50 ft, 3.0% at 100 ft, and 4.5% at 150 ft. NEC informational notes recommend (not mandate) ≤3% on a branch circuit and ≤5% combined feeder + branch.

Continuous loads (125%)

Loads that run 3+ hours (EV charging, electric heat) must be sized at 125%. That moves a 30A circuit to 8 copper / 8 aluminum.

Common 30 Amp Circuits

  • Electric clothes dryers
  • Window/through-wall AC units
  • 30A RV outlets (TT-30)
  • Water heaters

NEC Table 310.16 Ampacity Reference

Raw Table 310.16 ampacities (copper & aluminum, 60/75/90°C). Sizes whose usable 75°C ampacity meets 30A are highlighted. The 90°C column is only the basis for derating — terminations cap most installs at 60°C or 75°C.

Size (AWG/kcmil)Cu 60°CCu 75°CCu 90°CAl 75°CAl 90°C
14*152025
12*2025302025
10*3035403035
84050554045
65565755055
47085956575
3851001107585
29511513090100
1110130150100115
1/0125150170120135
2/0145175195135150
3/0165200225155175
4/0195230260180205
250 kcmil215255290205230
300 kcmil240285320230260
350 kcmil260310350250280
400 kcmil280335380270305
500 kcmil320380430310350
600 kcmil350420475340385
700 kcmil385460520375425
750 kcmil400475535385435

* 14, 12 and 10 AWG carry the tabulated ampacity but NEC 240.4(D) caps their overcurrent protection at 15A, 20A and 30A (copper) — so they cannot serve a higher-rated circuit even though the table value is larger.

Adjust for your exact run

Open the calculator pre-filled with 30A at 240V to add distance, temperature, and conductor count.

Open calculator