NEC Article 310 Wire Sizing Guide

Complete reference guide to National Electrical Code ampacity tables and conductor sizing requirements

Understanding NEC Article 310

Article 310 of the National Electrical Code covers conductors for general wiring and is fundamental to proper wire sizing. This article provides the ampacity tables that form the basis of safe electrical installations.

Key Sections of Article 310

310.12 - Insulation

Specifies insulation types and temperature ratings. Common ratings include:

  • 60°C: TW, UF
  • 75°C: THW, THWN, USE
  • 90°C: THHN, XHHW, USE-2

310.15 - Ampacity

Provides methods for determining conductor ampacity including:

  • • Temperature correction factors
  • • Adjustment factors for bundling
  • • Installation method considerations
  • • Ambient temperature effects

Table 310.16 - Allowable Ampacities

The most commonly referenced table for conductor ampacities. This table applies to not more than three current-carrying conductors in raceway, cable, or earth.

AWG/kcmilCopper 60°CCopper 75°CCopper 90°CAluminum 60°CAluminum 75°CAluminum 90°C
14152025---
12202530152025
10303540253035
8405055304045
6556575405055
4708595556575
2951151307590100
111013015085100115
1/0125150170100120135
2/0145175195115135150
3/0165200225130155175
4/0195230260150180205

Temperature Correction Factors

When ambient temperature differs from 30°C (86°F), ampacities must be corrected using Table 310.15(B)(1):

For 75°C Rated Conductors

21-25°C (70-77°F):1.08
26-30°C (78-86°F):1.00
31-35°C (87-95°F):0.91
36-40°C (96-104°F):0.82
41-45°C (105-113°F):0.71

Practical Application

If you have a 20A circuit with 12 AWG copper wire (25A at 75°C) in a 40°C attic:

Corrected Ampacity = 25A × 0.82 = 20.5A

The corrected ampacity (20.5A) is still adequate for the 20A circuit.

Adjustment Factors for Multiple Conductors

When more than three current-carrying conductors are installed in the same raceway, cable, or trench, ampacity must be reduced per Table 310.15(B)(3)(a):

4-6 conductors: 80%
7-9 conductors: 70%
10-20 conductors: 50%
21-30 conductors: 45%

Important Notes

  • • Neutral conductors carrying only unbalanced current are not counted
  • • Equipment grounding conductors are not counted
  • • Conductors that are not simultaneously energized are not counted
  • • Both temperature correction and adjustment factors may apply to the same installation

Special Applications

Motor Circuits (Article 430)

  • • Use 125% of motor full-load current for conductor sizing
  • • Branch circuit conductors must have ampacity ≥ 125% of FLA
  • • Feeder conductors use 125% of largest motor plus sum of others

Continuous Loads (Article 210)

  • • Loads expected to operate for 3+ hours continuously
  • • Conductor ampacity must be ≥ 125% of continuous load
  • • Plus 100% of non-continuous loads

Ready to Calculate?

Use our professional wire size calculator to apply these NEC requirements to your specific installation.

Use Wire Size Calculator