Conduit Sizing Guide

NEC Chapter 9 conduit fill tables and calculations for proper electrical raceway sizing

NEC Chapter 9 Requirements

Conduit fill is limited by NEC Chapter 9 to prevent overheating and ensure proper wire installation. These limits apply to all raceway types including EMT, rigid, and flexible conduit.

Conduit Fill Percentages

NEC Chapter 9, Table 1 specifies maximum fill percentages based on the number of conductors:

Number of ConductorsMaximum Fill PercentageTypical Applications
153%Service entrance, large feeders
231%120V/240V circuits
3 or more40%Multi-wire branch circuits

Common Conduit Types and Dimensions

EMT (Electrical Metallic Tubing)

Most common for commercial and residential installations. Lightweight and cost-effective.

Trade SizeInternal DiameterArea (sq in)40% Fill31% Fill53% Fill
1/2"0.622"0.3040.1220.0940.161
3/4"0.824"0.5330.2130.1650.283
1"1.049"0.8640.3460.2680.458
1 1/4"1.380"1.4960.5980.4640.793
1 1/2"1.610"2.0360.8140.6311.079
2"2.067"3.3561.3421.0401.779

Rigid Metal Conduit (RMC)

Heavy-duty applications, outdoor installations, and areas requiring maximum protection.

Trade SizeInternal DiameterArea (sq in)40% Fill31% Fill53% Fill
1/2"0.632"0.3140.1250.0970.166
3/4"0.836"0.5490.2200.1700.291
1"1.063"0.8870.3550.2750.470
1 1/4"1.394"1.5260.6100.4730.809
2"2.083"3.4081.3631.0571.806

Wire Areas for Common Sizes

NEC Chapter 9, Table 5 provides conductor dimensions including insulation for conduit fill calculations:

THWN-2 Copper Conductor Areas

AWGArea (sq in)
140.0097
120.0133
100.0211
80.0366
60.0507
40.0824
20.1158
10.1562

Common Installation Examples

Example 1: Three 12 AWG THWN-2 in EMT
Wire area: 3 × 0.0133 = 0.040 sq in
Minimum conduit: 1/2" EMT (0.122 sq in @ 40%)
Example 2: Two 4 AWG THWN-2 in EMT
Wire area: 2 × 0.0824 = 0.165 sq in
Minimum conduit: 3/4" EMT (0.165 sq in @ 31%)
Example 3: One 2/0 AWG THWN-2 in EMT
Wire area: 0.2223 sq in
Minimum conduit: 1" EMT (0.458 sq in @ 53%)

Derating for Conduit Fill

When more than three current-carrying conductors are in the same conduit, ampacity must be derated per NEC 310.15(B)(3)(a):

Ampacity Adjustment Factors

4-6 conductors
80% of ampacity
7-9 conductors
70% of ampacity
10-20 conductors
50% of ampacity
21-30 conductors
45% of ampacity

Special Considerations

Equipment Grounding Conductors

  • • Do not count toward fill calculations
  • • May be bare or insulated
  • • Still take up physical space
  • • Consider in practical installations

Neutral Conductors

  • • Count if carrying unbalanced current
  • • Don't count in balanced 3-wire circuits
  • • Always count in multiwire branch circuits
  • • Consider harmonic currents

Installation Best Practices

Tips for Successful Conduit Installation

Before Installation:

  • • Calculate fill percentages accurately
  • • Consider future circuit additions
  • • Plan pulling routes and angles
  • • Select appropriate lubricants

During Installation:

  • • Use proper pulling techniques
  • • Avoid exceeding pull tension limits
  • • Install pull boxes as needed
  • • Maintain minimum bend radii

Need Help with Wire and Conduit Sizing?

Use our wire size calculator to determine conductor requirements, then apply conduit fill tables for proper raceway sizing.

Calculate Wire & Conduit Size