About & Methodology
How the wire size, ampacity and voltage-drop results on this site are calculated from the 2023 National Electrical Code tables and formulas.
WireSizeCalculator.org is a free reference tool for sizing electrical conductors, breakers and voltage drop to the U.S. National Electrical Code. Ampacity values are read from the NEC tables below; voltage drop is calculated from the NEC Chapter 9 conductor resistance (current × resistance × round-trip length for single-phase and DC; × √3 × one-way length for three-phase).
Who runs this site
WireSizeCalculator.org is operated by Clooms (Shijiazhuang Cloom Tech., Ltd.), a wire-harness and cable-assembly business in Shijiazhuang, Hebei, China. The site is published by Hommer Zhao, Founder & General Manager of Clooms.
We work with wire and cable every day, but we are not licensed U.S. electricians and this site does not replace one. That is why every result is tied to a named NEC table and the safety disclaimer below applies. Corrections are welcome at support@wiresizecalculator.org.
How we verify accuracy
- Every result is generated from the 2023 NEC tables listed below — the same tables a licensed electrician uses.
- Automated tests check the calculator against known reference values (e.g. 50A → 8 AWG copper, 100A → 3 AWG, 200A → 3/0 at 75°C).
- We apply the rules that change the answer — the 240.4(D) small-conductor limits, 110.14(C) termination temperatures, the 125% continuous-load rule and voltage drop — rather than a single lookup.
- Content was last checked against the 2023 NEC tables in June 2026.
The NEC 2023 sources we use
| NEC reference | What it governs |
|---|---|
| Table 310.16 | Conductor ampacities (60 / 75 / 90°C, copper & aluminum) |
| 240.6(A) | Standard overcurrent device (breaker/fuse) sizes |
| 240.4(D) | Small-conductor overcurrent limits (14/12/10 AWG) |
| 110.14(C) | Termination temperature limits |
| 310.15(B)(1) | Ambient-temperature correction factors |
| 310.15(C)(1) | Conductor-bundling adjustment factors |
| 210.19 / 215.2 | Continuous-load 125% conductor sizing |
| Chapter 9, Table 8 | Conductor DC resistances (voltage drop) |
Safety disclaimer
This tool provides reference calculations only and is not a substitute for professional electrical engineering or design. Electrical work must comply with the edition of the NEC and any local amendments adopted in your jurisdiction, and with manufacturer instructions. Motors, HVAC and welders follow special rules (NEC 430/440/630). Always have installations designed and inspected by a licensed electrician. You assume all responsibility for use of this tool.