What Size Wire for 30 Amps at 50 Feet?

Voltage-drop-aware wire sizing for a 30-amp circuit running 50 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
10

Actual drop 1.5%. For ≤5% drop: 10 (1.5%).

Aluminum · ≤3% drop
8

Actual drop 1.6%. For ≤5% drop: 8 (1.6%).

At 50 ft, ampacity still governs: 10 AWG copper carries 30A and its drop (1.5%) is already within 3% — no upsizing needed.

Voltage Drop at 50 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 50 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
101.5%2.5%
81.0%1.6%
60.6%1.0%
40.4%0.6%
30.3%0.5%
20.2%0.4%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 30A, 240V, 50 ft to adjust material, temperature and drop target.

Open calculator

30 Amps at Other Distances