What Size Wire for 30 Amps at 200 Feet?
Voltage-drop-aware wire sizing for a 30-amp circuit running 200 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.
Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.
Actual drop 2.5%. For ≤5% drop: 8 (3.8%).
Actual drop 2.5%. For ≤5% drop: 6 (4.0%).
At 200 ft, voltage drop governs: ampacity alone would allow 10 AWG copper, but staying ≤3% requires upsizing to 6.
Voltage Drop at 200 Feet
Voltage drop is calculated for a 240V single-phase circuit over a 200 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.
| Wire size | Copper drop | Aluminum drop | Within 3%? |
|---|---|---|---|
| 10 | 6.0% | 10.0% | — |
| 8 | 3.8% | 6.3% | — |
| 6 | 2.5% | 4.0% | |
| 4 | 1.5% | 2.5% | |
| 3 | 1.2% | 2.0% | |
| 2 | 1.0% | 1.6% |
Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.
Different distance or voltage?
Open the calculator pre-filled with 30A, 240V, 200 ft to adjust material, temperature and drop target.