What Size Wire for 40 Amps at 300 Feet?

Voltage-drop-aware wire sizing for a 40-amp circuit running 300 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
3

Actual drop 2.5%. For ≤5% drop: 6 (4.9%).

Aluminum · ≤3% drop
1

Actual drop 2.5%. For ≤5% drop: 3 (4.0%).

At 300 ft, voltage drop governs: ampacity alone would allow 8 AWG copper, but staying ≤3% requires upsizing to 3.

Voltage Drop at 300 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 300 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
87.6%12.6%
64.9%8.1%
43.1%5.1%
32.5%4.0%
21.9%3.2%
11.5%2.5%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 40A, 240V, 300 ft to adjust material, temperature and drop target.

Open calculator

40 Amps at Other Distances