What Size Wire for 40 Amps at 25 Feet?

Voltage-drop-aware wire sizing for a 40-amp circuit running 25 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
8

Actual drop 0.6%. For ≤5% drop: 8 (0.6%).

Aluminum · ≤3% drop
8

Actual drop 1.1%. For ≤5% drop: 8 (1.1%).

At 25 ft, ampacity still governs: 8 AWG copper carries 40A and its drop (0.6%) is already within 3% — no upsizing needed.

Voltage Drop at 25 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 25 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
80.6%1.1%
60.4%0.7%
40.3%0.4%
30.2%0.3%
20.2%0.3%
10.1%0.2%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.