What Size Wire for 40 Amps at 100 Feet?
Voltage-drop-aware wire sizing for a 40-amp circuit running 100 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.
Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated June 2026.
Actual drop 2.5%. For ≤5% drop: 8 (2.5%).
Actual drop 2.7%. For ≤5% drop: 8 (4.2%).
At 100 ft, ampacity still governs: 8 AWG copper carries 40A and its drop (2.5%) is already within 3% — no upsizing needed.
Voltage Drop at 100 Feet
Voltage drop is calculated for a 240V single-phase circuit over a 100 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.
| Wire size | Copper drop | Aluminum drop | Within 3%? |
|---|---|---|---|
| 8 | 2.5% | 4.2% | |
| 6 | 1.6% | 2.7% | |
| 4 | 1.0% | 1.7% | |
| 3 | 0.8% | 1.3% | |
| 2 | 0.6% | 1.1% | |
| 1 | 0.5% | 0.8% |
Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.