What Size Wire for 20 Amps at 50 Feet?

Voltage-drop-aware wire sizing for a 20-amp circuit running 50 ft (one-way) at 120V — because over distance, voltage drop, not ampacity, often sets the wire size.

Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated June 2026.

Copper · ≤3% drop
10

Actual drop 2.0%. For ≤5% drop: 12 (3.2%).

Aluminum · ≤3% drop
8

Actual drop 2.1%. For ≤5% drop: 10 (3.3%).

At 50 ft, voltage drop governs: ampacity alone would allow 12 AWG copper, but staying ≤3% requires upsizing to 10.

Voltage Drop at 50 Feet

Voltage drop is calculated for a 120V single-phase circuit over a 50 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
123.2%5.3%—
102.0%3.3%
81.3%2.1%
60.8%1.3%
40.5%0.8%
30.4%0.7%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 20A, 120V, 50 ft to adjust material, temperature and drop target.

Open calculator