What Size Wire for 20 Amps at 150 Feet?

Voltage-drop-aware wire sizing for a 20-amp circuit running 150 ft (one-way) at 120V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
6

Actual drop 2.5%. For ≤5% drop: 8 (3.8%).

Aluminum · ≤3% drop
4

Actual drop 2.5%. For ≤5% drop: 6 (4.0%).

At 150 ft, voltage drop governs: ampacity alone would allow 12 AWG copper, but staying ≤3% requires upsizing to 6.

Voltage Drop at 150 Feet

Voltage drop is calculated for a 120V single-phase circuit over a 150 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
129.7%15.9%
106.0%10.0%
83.8%6.3%
62.5%4.0%
41.5%2.5%
31.2%2.0%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 20A, 120V, 150 ft to adjust material, temperature and drop target.

Open calculator

20 Amps at Other Distances