What Size Wire for 150 Amps at 75 Feet?

Voltage-drop-aware wire sizing for a 150-amp circuit running 75 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated June 2026.

Copper · ≤3% drop
1/0

Actual drop 1.1%. For ≤5% drop: 1/0 (1.1%).

Aluminum · ≤3% drop
3/0

Actual drop 1.2%. For ≤5% drop: 3/0 (1.2%).

At 75 ft, ampacity still governs: 1/0 AWG copper carries 150A and its drop (1.1%) is already within 3% — no upsizing needed.

Voltage Drop at 75 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 75 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
1/01.1%1.9%
2/00.9%1.5%
3/00.7%1.2%
4/00.6%0.9%
250 kcmil0.5%0.8%
300 kcmil0.4%0.7%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 150A, 240V, 75 ft to adjust material, temperature and drop target.