What Size Wire for 150 Amps at 100 Feet?

Voltage-drop-aware wire sizing for a 150-amp circuit running 100 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
1/0

Actual drop 1.5%. For ≤5% drop: 1/0 (1.5%).

Aluminum · ≤3% drop
3/0

Actual drop 1.6%. For ≤5% drop: 3/0 (1.6%).

At 100 ft, ampacity still governs: 1/0 AWG copper carries 150A and its drop (1.5%) is already within 3% — no upsizing needed.

Voltage Drop at 100 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 100 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
1/01.5%2.5%
2/01.2%2.0%
3/01.0%1.6%
4/00.8%1.3%
250 kcmil0.6%1.1%
300 kcmil0.5%0.9%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 150A, 240V, 100 ft to adjust material, temperature and drop target.

Open calculator

150 Amps at Other Distances