What Size Wire for 150 Amps at 25 Feet?
Voltage-drop-aware wire sizing for a 150-amp circuit running 25 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.
Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.
Actual drop 0.4%. For ≤5% drop: 1/0 (0.4%).
Actual drop 0.4%. For ≤5% drop: 3/0 (0.4%).
At 25 ft, ampacity still governs: 1/0 AWG copper carries 150A and its drop (0.4%) is already within 3% — no upsizing needed.
Voltage Drop at 25 Feet
Voltage drop is calculated for a 240V single-phase circuit over a 25 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.
| Wire size | Copper drop | Aluminum drop | Within 3%? |
|---|---|---|---|
| 1/0 | 0.4% | 0.6% | |
| 2/0 | 0.3% | 0.5% | |
| 3/0 | 0.2% | 0.4% | |
| 4/0 | 0.2% | 0.3% | |
| 250 kcmil | 0.2% | 0.3% | |
| 300 kcmil | 0.1% | 0.2% |
Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.
Different distance or voltage?
Open the calculator pre-filled with 150A, 240V, 25 ft to adjust material, temperature and drop target.