1/0 AWG Copper Wire Amp Rating & Ampacity
1/0 AWG copper wire carries 150A at 75°C (NEC Table 310.16), or 120A for aluminum; copper takes a 150A breaker, a standard rating equal to its ampacity.
Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated November 14, 2026.
1/0 AWG wire has an ampacity of 150A at 75°C for copper and 120A for aluminum (NEC Table 310.16). Its 60°C and 90°C copper ratings are 125A and 170A. Copper 1/0 AWG takes a 150A breaker (150A is a standard rating, so no 240.4(B) rounding is involved).
1/0 AWG Ampacity Chart: 60 °C, 75 °C and 90 °C (NEC Table 310.16)
Table 310.16 values at 30 °C ambient with no more than three current-carrying conductors in a raceway, cable or earth. Use the column of the lowest-rated part of the circuit (insulation, breaker or lug). 1/0 AWG is larger than 1 AWG, so NEC 110.14(C)(1)(b) allows the 75 °C column with 75 °C-rated terminations.
| 1/0 AWG | 60 °C (e.g. TW, UF) | 75 °C (e.g. THW, THWN, XHHW, USE) | 90 °C (e.g. THHN, THWN-2, XHHW-2) |
|---|---|---|---|
| Copper | 125 A | 150 A | 170 A |
| Aluminum / copper-clad aluminum | 100 A | 120 A | 135 A |
1/0 AWG Wire Specifications
| Ampacity — Copper (60 / 75 / 90°C) | 125 / 150 / 170 A |
| Ampacity — Aluminum (60 / 75 / 90°C) | 100 / 120 / 135 A |
| Cross-section | 105,600 circular mils |
| DC resistance — Copper | 0.122 Ω / 1000 ft |
| DC resistance — Aluminum | 0.201 Ω / 1000 ft |
| Calculated copper voltage drop (240V single-phase, one-way length) | 0.8% at 50 ft · 1.5% at 100 ft (at 150A); resistance-only estimate, AC drop can be higher |
1/0 AWG Ampacity by Wire Type
NEC Table 310.16 assumes 30 °C ambient and no more than three current-carrying conductors. Usable ampacity below is capped by the termination rating, before derating. THHN is for dry locations; THWN-2 and XHHW-2 have 90 °C wet/dry ratings. USE-2 alone is not a general-purpose interior wiring designation; verify the listing and location.
Swipe horizontally to see all columns.
| Wire type | NEC column | Table ampacity (A) | Usable ampacity (A) |
|---|---|---|---|
| THHN / THWN-2 copper | 90 °C table, 75 °C terminals | 170 | 150 |
| XHHW-2 copper | 90 °C table, 75 °C terminals | 170 | 150 |
| THW / THWN copper | 75 °C insulation and terminals | 150 | 150 |
| XHHW-2 / USE-2 aluminum | 90 °C table, 75 °C terminals | 135 | 120 |
| 60 °C terminations or 60 °C-limited equipment | 60 °C copper / aluminum | 125 / 100 | 125 / 100 |
NM-B (Romex) is not manufactured in 1/0 AWG; NEC 334.104 limits NM cable copper power conductors to 14 AWG through 2 AWG. NEC 110.14(C)(1)(b) allows the 75 °C column for conductors larger than 1 AWG when equipment is rated 75 °C. A 90 °C insulation rating alone does not permit loading 75 °C terminals to the 90 °C ampacity.
1/0 AWG Breaker Size (NEC 240.6(A) and 240.4(B))
Copper at 75 °C has an ampacity of 150 A, which is itself a standard rating in NEC 240.6(A), so a 150 A breaker matches the conductor and NEC 240.4(B) next-size-up does not come into play for copper. The calculated load must still fit 150 A, including continuous-load sizing at 125%. For aluminum, 125% of continuous load plus noncontinuous load must not exceed 120 A before any further derating; a larger permitted breaker does not increase conductor ampacity. Aluminum 1/0 AWG is rated 120 A, which is not a standard rating: use 110 A, or 125 A only when the 240.4(B) conditions apply (device no more than 800 A and not a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads).
Swipe horizontally to see all columns.
| Material (75 °C) | Conductor ampacity | Conservative breaker at or below | Next standard breaker |
|---|---|---|---|
| Copper | 150 A | 150 A | 150 A (already standard) |
| Aluminum | 120 A | 110 A | 125 A (conditional) |
Is 1/0 AWG Good for a 175 Amp Service? (NEC 310.12 83% Rule)
For qualifying 120/240 V single-phase dwelling services under NEC 310.12(A), and main feeders supplying the entire dwelling load under 310.12(B), conductor ampacity must be at least 83% of the service or feeder rating. It covers services and feeders rated 100 through 400 A, and applies to dwellings only; other occupancies use full Table 310.16 ampacity. Our service-sizing calculations (NEC 2023 inputs, computed November 14, 2026). Required ampacity = 0.83 × service rating. These comparisons assume 75 °C terminals and no additional derating.
Swipe horizontally to see all columns.
| Service (A) | Required ampacity (A) | Smallest copper | Smallest aluminum | 1/0 AWG Cu qualifies? | 1/0 AWG Al qualifies? |
|---|---|---|---|---|---|
| 125 | 103.75 | 2 AWG | 1/0 AWG | Yes | Yes |
| 150 | 124.5 | 1 AWG | 2/0 AWG | Yes | No |
| 175 | 145.25 | 1/0 AWG | 3/0 AWG | Yes | No |
| 200 | 166 | 2/0 AWG | 4/0 AWG | No | No |
| 225 | 186.75 | 3/0 AWG | 250 kcmil | No | No |
For a single conductor per phase, 1/0 AWG copper meets up to a 175 A dwelling service; aluminum meets up to 125 A among these standard ratings. A 225 A service requires 186.75 A: use at least 3/0 AWG copper or 250 kcmil aluminum under this rule. Outside dwellings (and for feeders that do not carry the entire dwelling load), the 83% allowance does not apply: 1/0 AWG copper is limited to its 150 A Table 310.16 rating.
How Far Can You Run 1/0 AWG? (3% Voltage Drop)
Our calculations (computed November 14, 2026). Method: L = floor(0.03 × V × 1000 ÷ (k × I × R)), where L is the one-way distance in feet, V is the line-to-line voltage, k = 2 for single-phase or √3 for three-phase, I is the load current and R is the Chapter 9 Table 8 DC resistance at 75 °C (uncoated copper 0.122 Ω/1000 ft, aluminum 0.201 Ω/1000 ft). Assumptions: noncontinuous load, 75 °C terminals, 30 °C ambient, no more than three current-carrying conductors and no adjustment factors. Only loads within each material's 75 °C ampacity are shown; a continuous load must be sized at 125%, so a 100 A continuous load needs conductors rated at least 125 A (1/0 AWG copper qualifies at 75 °C; aluminum does not). The 3% drop is a design target. Select a linked copper single-phase distance to open the calculator with those inputs.
Swipe horizontally to see all columns.
These are resistance-only preliminary estimates. Actual AC voltage drop depends on conductor resistance, reactance, power factor and the installation (conduit material, spacing); for large conductors NEC Chapter 9 Table 9 effective impedance can exceed DC resistance, especially in steel conduit, so real distances can be shorter. Check AC impedance before final sizing.
1/0 AWG Ampacity After Derating
For 90 °C insulation, multiply the 90 °C column by the ambient correction and current-carrying conductor (CCC) adjustment factors from NEC 310.15(B)/(C), then cap at 75 °C: 150 A copper or 120 A aluminum. Each value links to the ampacity calculator with the same inputs; the calculator shows the raw derated value, so apply the 75 °C termination cap shown here manually.
Swipe horizontally to see all columns.
| Ambient | CCC | Copper raw → usable (A) | Aluminum raw → usable (A) |
|---|---|---|---|
| 30 °C | 3 | 170.0 → 150 | 135.0 → 120 |
| 40 °C | 3 | 154.7 → 150 | 122.9 → 120 |
| 30 °C | 4–6 | 136.0 → 136 | 108.0 → 108 |
| 40 °C | 4–6 | 123.8 → 123.8 | 98.3 → 98.3 |
| 30 °C | 7–9 | 119.0 → 119 | 94.5 → 94.5 |
| 40 °C | 7–9 | 108.3 → 108.3 | 86.0 → 86 |
Parallel 1/0 AWG Sets
Our parallel-set calculations (NEC 2023 inputs, computed November 14, 2026). NEC 310.10(G) allows paralleling conductors 1/0 AWG and larger. This table assumes balanced three-phase sets with three CCC per set, 90 °C insulation, 75 °C terminals and 30 °C ambient. Separate raceways have three CCC each; a shared raceway contains all phase conductors and requires adjustment. When parallel sets run in separate raceways, each raceway must contain a complete set of circuit conductors (every phase, plus the neutral if used) under NEC 300.3(B)(1), and the separate cables or raceways must contain the same number of conductors and have the same electrical characteristics under 310.10(G)(3).
Swipe horizontally to see all columns.
| Sets | Shared raceway CCC / factor | Copper separate raceways (A) | Copper shared raceway (A) | Aluminum separate raceways (A) | Aluminum shared raceway (A) |
|---|---|---|---|---|---|
| 2 | 6 / 80% | 300 | 272 | 240 | 216 |
| 3 | 9 / 70% | 450 | 357 | 360 | 283.5 |
Shared-raceway totals equal the number of sets × the lesser of adjusted 90 °C ampacity and 75 °C ampacity. Neutral and equipment grounding conductor (EGC) sizing are not covered; additional counted neutrals change adjustment. Within each paralleled phase, neutral or grounded-conductor group, the conductors must match in length, material, circular-mil area, insulation type and termination method under 310.10(G)(2). These totals are conductor ampacities, not automatic breaker selections.
1/0 AWG Copper vs Aluminum: Equivalent Sizes
To meet 1/0 AWG copper's 150 A rating at 75 °C, the smallest tabulated aluminum size is 3/0 AWG (155 A). To meet 1/0 AWG aluminum's 120 A rating, use at least 1 AWG copper (130 A). At the same 1/0 AWG cross-section, aluminum's DC resistance is 1.65 times copper's (our calculation: 0.201 ÷ 0.122 Ω/kft); equal ampacity does not guarantee equal voltage drop.
1/0 AWG Diameter and Cross-Section
Swipe horizontally to see all columns.
| Bare conductor property | Value |
|---|---|
| Strands (Chapter 9 Table 8) | 19 |
| Overall bare stranded diameter | 0.372 in / 9.45 mm |
| Bare stranded overall area (Table 8) | 0.109 in² |
| Nominal metal cross-section | 105,600 circular mils / 53.5 mm² |
The Table 8 figures describe the bare stranded conductor, including its overall strand envelope. The 0.325 in figure some wire charts list for 1/0 AWG is the diameter of a solid round conductor with the same metal area; the stranded conductor is larger (0.372 in) because of the gaps between strands. Metal area is computed as circular mils × 0.0005067 mm². Insulated outside diameter for THHN or XHHW is larger; obtain it from Chapter 9 Table 5 or manufacturer data for conduit-fill calculations.
1/0 AWG Wire FAQ
How many amps is 1/0 AWG good for?
1/0 AWG copper is rated 125/150/170 A at 60/75/90 °C; aluminum is 100/120/135 A (NEC Table 310.16). With 75 °C terminals, use 150 A copper or 120 A aluminum before derating and load checks.
Is 1/0 AWG the same as 1 gauge or 0 gauge wire?
1/0 AWG ("one-aught", also written 0 AWG) is not the same as 1 AWG. It is one size larger: 105,600 circular mils (about 53.5 mm²) versus 83,690 for 1 AWG, and it carries 150 A copper at 75 °C versus 130 A. The next size up is 2/0 AWG (175 A copper at 75 °C).
Is 1/0 AWG copper good for a 175 amp service?
For a qualifying 120/240 V dwelling service, yes: NEC 310.12 requires 145.25 A, and 1/0 AWG copper is rated 150 A at 75 °C (no additional derating). Outside dwellings, the 83% allowance does not apply and the conductor ampacity stays 150 A; there a 175 A device is not permitted on 1/0 AWG copper, because 150 A is itself a standard rating and 240.4(B) next-size-up does not apply. In aluminum, the same dwelling service needs 3/0 AWG or larger (1/0 AWG aluminum is rated 120 A).
What size breaker for 1/0 AWG copper?
At 75 °C, 1/0 AWG copper is rated 150 A, which is itself a standard breaker rating in NEC 240.6(A), so the matching breaker is 150 A; NEC 240.4(B) next-size-up does not apply. The calculated load must remain within 150 A, and a continuous load is sized at 125% (150 A of conductor ampacity covers 120 A continuous). 1/0 AWG aluminum (120 A) takes a 110 A breaker or 125 A under 240.4(B).
What is the ampacity of 1/0 AWG aluminum?
1/0 AWG aluminum is rated 100 A at 60 °C, 120 A at 75 °C and 135 A at 90 °C. With 75 °C equipment use 120 A before derating, with a 110 A breaker (conservative) or 125 A where NEC 240.4(B) next-size-up applies. It meets up to the 125 A qualifying dwelling-service requirement under NEC 310.12.
Why do some charts list 1/0 cable at 200 A or more?
Those figures are usually welding-cable or free-air ratings published by cable makers, not NEC Table 310.16 ampacities for building wire in raceway, cable or earth. Welding leads are sized under NEC Article 630 and the manufacturer's duty-cycle data. For a feeder, service or branch circuit, use the Table 310.16 value for the insulation type (125/150/170 A copper at 60/75/90 °C), limited by the termination rating.
Sources (NEC values on this page checked against these references on November 14, 2026)
- NEC 2023 Table 310.16 (ampacities); 240.4(B) and 240.6(A) (breakers); 310.12 (dwelling services); 310.10(G) and 300.3(B)(1) (parallel conductors).
- NEC 310.15(B)/(C) (ambient and adjustment factors); 110.14(C) (terminations); 334.104 (NM sizes); Chapter 9 Table 8 (uncoated copper and aluminum DC resistance, stranding) and Table 9 (AC impedance).
- Distance, service, derating and parallel tables are this site's own calculations from those NEC 2023 inputs; the calculation engine is unit-tested against the Table 310.16 values.
- NFPA 70 free access and standard information
Common Uses for 1/0 AWG Wire
- Copper feeders and subpanels up to 150 A where every termination is rated 75 °C and the calculated load (125% of continuous load plus noncontinuous load) fits (NEC 110.14(C)(1)(b) uses the 75 °C column for conductors larger than 1 AWG)
- 175 A qualifying dwelling services in copper under NEC 310.12 (75 °C terminations, no additional derating)
- 125 A qualifying dwelling services in aluminum under NEC 310.12 (75 °C terminations, no additional derating)
- EV charging (a continuous load sized at 125%): the calculated conductor-only ceiling for 1/0 AWG copper is 150 ÷ 1.25 = 120 A continuous, before any further derating and assuming listed 75 °C terminations and separately compliant overcurrent protection; e.g. a charger drawing 100 A continuously needs 125 A of conductor ampacity; follow NEC Article 625 and the charger's installation manual
- Paralleled feeders: 1/0 AWG is the smallest size NEC 310.10(G) allows in general-use parallel sets; two copper sets in separate raceways give 300 A of conductor ampacity before further corrections
- Welders and motors are sized from the nameplate input current and duty cycle (NEC Article 630) or motor full-load current (Article 430), not from welding output amps, so check those rules before using 1/0 AWG