2/0 Wire Ampacity & Specifications

NEC ampacity, resistance and typical uses for 2/0 copper and aluminum wire.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper 75°C
175A
Copper 90°C
195A
Aluminum 75°C
135A
Typical breaker
175A

2/0 Wire Specifications

Ampacity — Copper (60 / 75 / 90°C)145 / 175 / 195 A
Ampacity — Aluminum (60 / 75 / 90°C)115 / 135 / 150 A
Cross-section133,100 circular mils
DC resistance — Copper0.0967 Ω / 1000 ft
DC resistance — Aluminum0.159 Ω / 1000 ft
Typical voltage drop (240V)0.7% at 50 ft · 1.4% at 100 ft (at 175A)

Common Uses for 2/0 Wire

  • 145–175A feeders
  • 150–175A copper feeders
Ampacities are from NEC Table 310.16. 14, 12 and 10 AWG are limited to 15A, 20A and 30A overcurrent protection (240.4(D)). Terminations rated 60°C or 75°C usually cap the usable ampacity below the 90°C value.

Sizing a circuit?

Use the calculator to size wire for your current, distance and voltage.

Open calculator