3/0 Wire Ampacity & Specifications

NEC ampacity, resistance and typical uses for 3/0 copper and aluminum wire.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper 75°C
200A
Copper 90°C
225A
Aluminum 75°C
155A
Typical breaker
200A

3/0 Wire Specifications

Ampacity — Copper (60 / 75 / 90°C)165 / 200 / 225 A
Ampacity — Aluminum (60 / 75 / 90°C)130 / 155 / 175 A
Cross-section167,800 circular mils
DC resistance — Copper0.0766 Ω / 1000 ft
DC resistance — Aluminum0.126 Ω / 1000 ft
Typical voltage drop (240V)0.6% at 50 ft · 1.3% at 100 ft (at 200A)

Common Uses for 3/0 Wire

  • 165–200A services and feeders
  • 200A copper services (general)
Ampacities are from NEC Table 310.16. 14, 12 and 10 AWG are limited to 15A, 20A and 30A overcurrent protection (240.4(D)). Terminations rated 60°C or 75°C usually cap the usable ampacity below the 90°C value.