250 kcmil Wire Ampacity & Specifications
NEC ampacity, resistance and typical uses for 250 kcmil copper and aluminum wire.
Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.
Copper 75°C
255A
Copper 90°C
290A
Aluminum 75°C
205A
Typical breaker
250A
250 kcmil Wire Specifications
| Ampacity — Copper (60 / 75 / 90°C) | 215 / 255 / 290 A |
| Ampacity — Aluminum (60 / 75 / 90°C) | 170 / 205 / 230 A |
| Cross-section | 250,000 circular mils |
| DC resistance — Copper | 0.0515 Ω / 1000 ft |
| DC resistance — Aluminum | 0.0847 Ω / 1000 ft |
| Typical voltage drop (240V) | 0.5% at 50 ft · 1.1% at 100 ft (at 250A) |
Common Uses for 250 kcmil Wire
- 255A copper feeders
- Commercial distribution
Ampacities are from NEC Table 310.16. 14, 12 and 10 AWG are limited to 15A, 20A and 30A overcurrent protection (240.4(D)). Terminations rated 60°C or 75°C usually cap the usable ampacity below the 90°C value.
Sizing a circuit?
Use the calculator to size wire for your current, distance and voltage.