350 kcmil (350 MCM) Wire Ampacity & Specifications
350 kcmil copper wire carries 310A at 75°C (NEC Table 310.16), or 250A for aluminum; copper takes a 300A breaker (conservative) or 350A where NEC 240.4(B) applies.
Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated November 7, 2026.
350 kcmil wire has an ampacity of 310A at 75°C for copper and 250A for aluminum (NEC Table 310.16). Its 60°C and 90°C copper ratings are 260A and 350A. Copper 350 kcmil takes a 300A breaker (conservative) or 350A when the NEC 240.4(B) next-size-up conditions apply.
350 kcmil Wire Specifications
| Ampacity — Copper (60 / 75 / 90°C) | 260 / 310 / 350 A |
| Ampacity — Aluminum (60 / 75 / 90°C) | 210 / 250 / 280 A |
| Cross-section | 350,000 circular mils |
| DC resistance — Copper | 0.0367 Ω / 1000 ft |
| DC resistance — Aluminum | 0.0605 Ω / 1000 ft |
| Calculated copper voltage drop (240V single-phase, one-way length) | 0.5% at 50 ft · 0.9% at 100 ft (at 300A); resistance-only estimate, AC drop can be higher |
350 kcmil Ampacity by Wire Type
NEC Table 310.16 assumes 30 °C ambient and no more than three current-carrying conductors. Usable ampacity below is capped by the termination rating, before derating. THHN is for dry locations; THWN-2 and XHHW-2 have 90 °C wet/dry ratings. USE-2 alone is not a general-purpose interior wiring designation; verify the listing and location.
Swipe horizontally to see all columns.
| Wire type | NEC column | Table ampacity (A) | Usable ampacity (A) |
|---|---|---|---|
| THHN / THWN-2 copper | 90 °C table, 75 °C terminals | 350 | 310 |
| XHHW-2 copper | 90 °C table, 75 °C terminals | 350 | 310 |
| THW / THWN copper | 75 °C insulation and terminals | 310 | 310 |
| XHHW-2 / USE-2 aluminum | 90 °C table, 75 °C terminals | 280 | 250 |
| 60 °C terminations or 60 °C-limited equipment | 60 °C copper / aluminum | 260 / 210 | 260 / 210 |
NM-B (Romex) is not manufactured in 350 kcmil; NEC 334.104 limits NM cable copper power conductors to 14 AWG through 2 AWG. NEC 110.14(C)(1)(b) allows the 75 °C column for conductors larger than 1 AWG when equipment is rated 75 °C. A 90 °C insulation rating alone does not permit loading 75 °C terminals to the 90 °C ampacity.
350 kcmil Breaker Size (NEC 240.4(B))
Copper at 75 °C has an ampacity of 310 A, which is not a standard rating in NEC 240.6(A). NEC 240.4(B) permits the next higher standard breaker, 350 A, when the device does not exceed 800 A and the circuit is not a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads. The calculated load must still fit the conductor ampacity, including continuous-load sizing. Rounding up does not increase ampacity.
Swipe horizontally to see all columns.
| Material (75 °C) | Conductor ampacity | Conservative breaker at or below | Next standard breaker |
|---|---|---|---|
| Copper | 310 A | 300 A | 350 A (conditional) |
| Aluminum | 250 A | 250 A | 250 A (already standard) |
Is 350 kcmil Good for a 400 Amp Service? (NEC 310.12 83% Rule)
For qualifying 120/240 V single-phase dwelling services under NEC 310.12(A), and main feeders supplying the entire dwelling load under 310.12(B), conductor ampacity must be at least 83% of the service or feeder rating. It covers services and feeders rated 100 through 400 A, and applies to dwellings only; other occupancies use full Table 310.16 ampacity. Our service-sizing calculations (NEC 2023 inputs, computed November 7, 2026). Required ampacity = 0.83 × service rating. These comparisons assume 75 °C terminals and no additional derating.
Swipe horizontally to see all columns.
| Service (A) | Required ampacity (A) | Smallest copper | Smallest aluminum | 350 kcmil Cu qualifies? | 350 kcmil Al qualifies? |
|---|---|---|---|---|---|
| 200 | 166 | 2/0 AWG | 4/0 AWG | Yes | Yes |
| 225 | 186.75 | 3/0 AWG | 250 kcmil | Yes | Yes |
| 250 | 207.5 | 4/0 AWG | 300 kcmil | Yes | Yes |
| 300 | 249 | 250 kcmil | 350 kcmil | Yes | Yes |
| 350 | 290.5 | 350 kcmil | 500 kcmil | Yes | No |
| 400 | 332 | 400 kcmil | 600 kcmil | No | No |
For a single conductor per phase, 350 kcmil copper meets up to a 350 A dwelling service; aluminum meets up to 300 A among these standard ratings. A 400 A service requires 332 A: use at least 400 kcmil copper or 600 kcmil aluminum under this rule.
How Far Can You Run 350 kcmil? (3% Voltage Drop)
Our calculations (computed November 7, 2026). Method: L = floor(0.03 × V × 1000 ÷ (k × I × R)), where L is the one-way distance in feet, V is the line-to-line voltage, k = 2 for single-phase or √3 for three-phase, I is the load current and R is the Chapter 9 Table 8 DC resistance at 75 °C (uncoated copper 0.0367 Ω/1000 ft, aluminum 0.0605 Ω/1000 ft). Assumptions: noncontinuous load, 75 °C terminals, 30 °C ambient, no more than three current-carrying conductors and no adjustment factors. Only loads within each material's 75 °C ampacity are shown; a continuous load must be sized at 125%, so a 300 A continuous load needs conductors rated at least 375 A. The 3% drop is a design target. Select a linked copper single-phase distance to open the calculator with those inputs.
Swipe horizontally to see all columns.
These are resistance-only preliminary estimates. Actual AC voltage drop depends on conductor resistance, reactance, power factor and the installation (conduit material, spacing); for large conductors NEC Chapter 9 Table 9 effective impedance can exceed DC resistance, especially in steel conduit, so real distances can be shorter. Check AC impedance before final sizing.
350 kcmil Ampacity After Derating
For 90 °C insulation, multiply the 90 °C column by the ambient correction and current-carrying conductor (CCC) adjustment factors from NEC 310.15(B)/(C), then cap at 75 °C: 310 A copper or 250 A aluminum. Each value links to the ampacity calculator with the same inputs; the calculator shows the raw derated value, so apply the 75 °C termination cap shown here manually.
Swipe horizontally to see all columns.
| Ambient | CCC | Copper raw → usable (A) | Aluminum raw → usable (A) |
|---|---|---|---|
| 30 °C | 3 | 350.0 → 310 | 280.0 → 250 |
| 40 °C | 3 | 318.5 → 310 | 254.8 → 250 |
| 30 °C | 4–6 | 280.0 → 280 | 224.0 → 224 |
| 40 °C | 4–6 | 254.8 → 254.8 | 203.8 → 203.8 |
| 30 °C | 7–9 | 245.0 → 245 | 196.0 → 196 |
| 40 °C | 7–9 | 222.9 → 222.9 | 178.4 → 178.4 |
Parallel 350 kcmil Sets
Our parallel-set calculations (NEC 2023 inputs, computed November 7, 2026). NEC 310.10(G) allows paralleling conductors 1/0 AWG and larger. This table assumes balanced three-phase sets with three CCC per set, 90 °C insulation, 75 °C terminals and 30 °C ambient. Separate raceways have three CCC each; a shared raceway contains all phase conductors and requires adjustment. When parallel sets run in separate raceways, each raceway must contain a complete set of circuit conductors (every phase, plus the neutral if used) under NEC 300.3(B)(1), and the separate cables or raceways must contain the same number of conductors and have the same electrical characteristics under 310.10(G)(3).
Swipe horizontally to see all columns.
| Sets | Shared raceway CCC / factor | Copper separate raceways (A) | Copper shared raceway (A) | Aluminum separate raceways (A) | Aluminum shared raceway (A) |
|---|---|---|---|---|---|
| 2 | 6 / 80% | 620 | 560 | 500 | 448 |
| 3 | 9 / 70% | 930 | 735 | 750 | 588 |
Shared-raceway totals equal the number of sets × the lesser of adjusted 90 °C ampacity and 75 °C ampacity. Neutral and equipment grounding conductor (EGC) sizing are not covered; additional counted neutrals change adjustment. Within each paralleled phase, neutral or grounded-conductor group, the conductors must match in length, material, circular-mil area, insulation type and termination method under 310.10(G)(2). These totals are conductor ampacities, not automatic breaker selections.
350 kcmil Copper vs Aluminum: Equivalent Sizes
To meet 350 kcmil copper's 310 A rating at 75 °C, the smallest tabulated aluminum size is 500 kcmil (310 A). To meet 350 kcmil aluminum's 250 A rating, use at least 250 kcmil copper (255 A). At the same 350 kcmil cross-section, aluminum's DC resistance is 1.65 times copper's (our calculation: 0.0605 ÷ 0.0367 Ω/kft); equal ampacity does not guarantee equal voltage drop.
350 kcmil Diameter and Cross-Section
Swipe horizontally to see all columns.
| Bare conductor property | Value |
|---|---|
| Strands (Chapter 9 Table 8) | 37 |
| Overall bare stranded diameter | 0.681 in / 17.30 mm |
| Bare stranded overall area (Table 8) | 0.364 in² |
| Nominal metal cross-section | 350,000 circular mils / 177.3 mm² |
The Table 8 figures describe the bare stranded conductor, including its overall strand envelope. The 0.592 in figure some wire charts list for 350 kcmil is the diameter of a solid round conductor with the same metal area; the stranded conductor is larger (0.681 in) because of the gaps between strands. Metal area is computed as circular mils × 0.0005067 mm². Insulated outside diameter for THHN or XHHW is larger; obtain it from Chapter 9 Table 5 or manufacturer data for conduit-fill calculations.
350 kcmil Wire FAQ
How many amps is 350 kcmil good for?
350 kcmil copper is rated 260/310/350 A at 60/75/90 °C; aluminum is 210/250/280 A (NEC Table 310.16). With 75 °C terminals, use 310 A copper or 250 A aluminum before derating and load checks.
Is 350 MCM the same as 350 kcmil?
Yes. MCM is the older name for thousand circular mils; 350 MCM and 350 kcmil both mean 350,000 circular mils, approximately 177.3 mm².
Is 350 kcmil copper good for a 400 amp service?
No, a single conductor per phase is insufficient. NEC 310.12 requires 332 A for a qualifying 400 A dwelling service, exceeding its 310 A rating. The smallest table sizes meeting that requirement are 400 kcmil copper or 600 kcmil aluminum. 350 kcmil copper meets the 350 A dwelling-service requirement.
What size breaker for 350 kcmil copper?
At 75 °C, its 310 A ampacity falls between standard breaker ratings. A conservative breaker is 300 A; NEC 240.4(B) permits 350 A only when its next-size-up conditions apply (device no more than 800 A and not a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads). The calculated load must remain within conductor ampacity; continuous-load sizing still applies.
What is the ampacity of 350 kcmil aluminum?
350 kcmil aluminum is rated 210 A at 60 °C, 250 A at 75 °C and 280 A at 90 °C. With 75 °C equipment use 250 A before derating, with a 250 A standard breaker. It meets up to the 300 A qualifying dwelling-service requirement under NEC 310.12.
Sources (NEC values on this page checked against these references on November 7, 2026)
- NEC 2023 Table 310.16 (ampacities); 240.4(B) and 240.6(A) (breakers); 310.12 (dwelling services); 310.10(G) and 300.3(B)(1) (parallel conductors).
- NEC 310.15(B)/(C) (ambient and adjustment factors); 110.14(C) (terminations); 334.104 (NM sizes); Chapter 9 Table 8 (uncoated copper and aluminum DC resistance, stranding) and Table 9 (AC impedance).
- Distance, service, derating and parallel tables are this site's own calculations from those NEC 2023 inputs; the calculation engine is unit-tested against the Table 310.16 values.
- NFPA 70 free access and standard information
Common Uses for 350 kcmil Wire
- Copper feeders up to 310 A where the calculated load (125% of continuous load plus noncontinuous load) fits the 75 °C rating
- 350 A qualifying dwelling services in copper under NEC 310.12 (75 °C terminations, no additional derating)
- 300 A qualifying dwelling services in aluminum under NEC 310.12 (75 °C terminations, no additional derating)
- Two copper sets in separate raceways: 620 A conductor ampacity before further corrections (breaker and load selection are separate checks)