14 Wire Ampacity & Specifications

NEC ampacity, resistance and typical uses for 14 copper and aluminum wire.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper 75°C
20A
Copper 90°C
25A
Aluminum 75°C
Typical breaker
15A

14 Wire Specifications

Ampacity — Copper (60 / 75 / 90°C)15 / 20 / 25 A
Ampacity — Aluminum (60 / 75 / 90°C) / / A
Cross-section4,110 circular mils
DC resistance — Copper3.07 Ω / 1000 ft
DC resistance — Aluminum5.06 Ω / 1000 ft
Typical voltage drop (240V)1.9% at 50 ft · 3.8% at 100 ft (at 15A)

Common Uses for 14 Wire

  • 15A lighting and receptacle branch circuits
  • Residential general-purpose wiring
Ampacities are from NEC Table 310.16. 14, 12 and 10 AWG are limited to 15A, 20A and 30A overcurrent protection (240.4(D)). Terminations rated 60°C or 75°C usually cap the usable ampacity below the 90°C value.