What Size Wire for an Air Compressor?

Wire and breaker sizing for an Air Compressor — the typical 240V circuit, plus the code details (NEC 310.16) that change the answer.

Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated June 2026.

Copper
10 AWG

On a 30A 240V circuit at 75°C terminations.

Aluminum
8

Protected by a 30A breaker (NEC 240.6).

Voltage
240V
Breaker
30A
Connection
Hardwired
GFCI
Not required

Air Compressor current varies by model. The size above is the common case — always size the conductor to the unit’s nameplate rating and protect it at the labeled maximum breaker/fuse.

Air Compressor Circuit Details

  • Size to the motor FLA × 125%. A 240V 3–5 HP compressor typically needs a 30A circuit (10 AWG).
  • Hard-starting motors benefit from a dedicated circuit to avoid voltage sag.
  • Confirm 120V vs 240V — many shop compressors are convertible.

Long run to your air compressor?

Over distance, voltage drop can require a larger wire than the table above. See the 30A wire size by distance:

Size it for your exact install

Open the calculator pre-filled with 30A at 240V to add distance, material and temperature.

Open calculator