What Size Wire for 80 Amps at 200 Feet?

Voltage-drop-aware wire sizing for a 80-amp circuit running 200 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
2

Actual drop 2.6%. For ≤5% drop: 4 (4.1%).

Aluminum · ≤3% drop
1/0

Actual drop 2.7%. For ≤5% drop: 2 (4.3%).

At 200 ft, voltage drop governs: ampacity alone would allow 4 AWG copper, but staying ≤3% requires upsizing to 2.

Voltage Drop at 200 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 200 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
44.1%6.8%
33.3%5.4%
22.6%4.3%
12.1%3.4%
1/01.6%2.7%
2/01.3%2.1%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 80A, 240V, 200 ft to adjust material, temperature and drop target.

Open calculator