What Size Wire for 80 Amps at 150 Feet?
Voltage-drop-aware wire sizing for a 80-amp circuit running 150 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.
Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated June 2026.
Actual drop 2.5%. For ≤5% drop: 4 (3.1%).
Actual drop 2.5%. For ≤5% drop: 2 (3.2%).
At 150 ft, voltage drop governs: ampacity alone would allow 4 AWG copper, but staying ≤3% requires upsizing to 3.
Voltage Drop at 150 Feet
Voltage drop is calculated for a 240V single-phase circuit over a 150 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.
| Wire size | Copper drop | Aluminum drop | Within 3%? |
|---|---|---|---|
| 4 | 3.1% | 5.1% | — |
| 3 | 2.5% | 4.0% | |
| 2 | 1.9% | 3.2% | |
| 1 | 1.5% | 2.5% | |
| 1/0 | 1.2% | 2.0% | |
| 2/0 | 1.0% | 1.6% |
Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.
Different distance or voltage?
Open the calculator pre-filled with 80A, 240V, 150 ft to adjust material, temperature and drop target.