What Size Wire for 80 Amps at 100 Feet?

Voltage-drop-aware wire sizing for a 80-amp circuit running 100 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
4

Actual drop 2.1%. For ≤5% drop: 4 (2.1%).

Aluminum · ≤3% drop
2

Actual drop 2.1%. For ≤5% drop: 2 (2.1%).

At 100 ft, ampacity still governs: 4 AWG copper carries 80A and its drop (2.1%) is already within 3% — no upsizing needed.

Voltage Drop at 100 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 100 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
42.1%3.4%
31.6%2.7%
21.3%2.1%
11.0%1.7%
1/00.8%1.3%
2/00.6%1.1%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 80A, 240V, 100 ft to adjust material, temperature and drop target.

Open calculator

80 Amps at Other Distances