What Size Wire for 60 Amps at 150 Feet?

Voltage-drop-aware wire sizing for a 60-amp circuit running 150 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
4

Actual drop 2.3%. For ≤5% drop: 6 (3.7%).

Aluminum · ≤3% drop
2

Actual drop 2.4%. For ≤5% drop: 4 (3.8%).

At 150 ft, voltage drop governs: ampacity alone would allow 6 AWG copper, but staying ≤3% requires upsizing to 4.

Voltage Drop at 150 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 150 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
63.7%6.1%
42.3%3.8%
31.8%3.0%
21.5%2.4%
11.2%1.9%
1/00.9%1.5%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 60A, 240V, 150 ft to adjust material, temperature and drop target.

Open calculator