3 Wire Ampacity & Specifications

NEC ampacity, resistance and typical uses for 3 copper and aluminum wire.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper 75°C
100A
Copper 90°C
110A
Aluminum 75°C
75A
Typical breaker
100A

3 Wire Specifications

Ampacity — Copper (60 / 75 / 90°C)85 / 100 / 110 A
Ampacity — Aluminum (60 / 75 / 90°C)65 / 75 / 85 A
Cross-section52,620 circular mils
DC resistance — Copper0.245 Ω / 1000 ft
DC resistance — Aluminum0.403 Ω / 1000 ft
Typical voltage drop (240V)1.0% at 50 ft · 2.0% at 100 ft (at 100A)

Common Uses for 3 Wire

  • 85–100A feeders
  • 100A sub-panel feeders (copper)
Ampacities are from NEC Table 310.16. 14, 12 and 10 AWG are limited to 15A, 20A and 30A overcurrent protection (240.4(D)). Terminations rated 60°C or 75°C usually cap the usable ampacity below the 90°C value.

Sizing a circuit?

Use the calculator to size wire for your current, distance and voltage.

Open calculator