6 AWG Wire Ampacity & Specifications

6 AWG copper wire carries 65A at 75°C (NEC Table 310.16), or 50A for aluminum; copper is typically protected by a 60A breaker.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last updated June 2026.

6 AWG wire has an ampacity of 65A at 75°C for copper and 50A for aluminum (NEC Table 310.16). Its 60°C and 90°C copper ratings are 55A and 75A. Copper 6 AWG is commonly protected by a 60A breaker.

Copper 75°C
65A
Copper 90°C
75A
Aluminum 75°C
50A
Copper breaker (75°C)
60A

6 AWG Wire Specifications

Ampacity — Copper (60 / 75 / 90°C)55 / 65 / 75 A
Ampacity — Aluminum (60 / 75 / 90°C)40 / 50 / 55 A
Cross-section26,240 circular mils
DC resistance — Copper0.491 Ω / 1000 ft
DC resistance — Aluminum0.808 Ω / 1000 ft
Typical voltage drop (240V)1.2% at 50 ft · 2.5% at 100 ft (at 60A)

6 AWG Ampacity by Wire Type

The same 6 AWG conductor gets a different ampacity depending on the cable type and the terminal rating. "Usable" is the conductor ampacity before ambient or bundling adjustment; how much load the circuit may carry and the breaker size are separate checks (below). Assumes 30 °C ambient and no more than three current-carrying conductors. THHN is rated 90 °C in dry locations; THWN-2 is 90 °C wet or dry; NM-B is for dry locations; UF-B can be direct-buried.

Wire typeNEC columnTable ampacityUsable
THHN / THWN-2 copper in conduit90 °C table, 75 °C terminals75 A65 A
THW / THWN copper (75 °C)75 °C insulation and terminals65 A65 A
NM-B (Romex) copper60 °C (NEC 334.80)55 A55 A
UF-B copper60 °C (NEC 340.80)55 A55 A
XHHW-2 aluminum90 °C table, 75 °C terminals55 A50 A

6 AWG Breaker Size: 50, 60 or 70 A?

  • Copper THHN/THWN-2 or THWN, 75 °C terminals: 60 A. 65 A is the conductor ampacity, not a standard breaker size (NEC 240.6(A)), so the usual breaker is 60 A.
  • Aluminum, 75 °C terminals: 50 A. 6 AWG aluminum is rated 50 A, a standard size, so no rounding applies.
  • NM-B (Romex): 50 A circuit. The cable is limited to 55 A; NEC 240.4(B) may allow the next standard device (60 A) for a single, non-receptacle load, but it does not raise the cable's ampacity.
  • 70 A on 65 A copper is possible only under the 240.4(B) next-size-up conditions, and the load must still stay within 65 A.
  • Continuous loads (3 hours or more) are limited to 80% of the breaker and to the conductor ampacity ÷ 1.25: 48 A on a 60 A copper THHN/THWN-2 circuit, 40 A on a 50 A aluminum circuit, and 44 A on 6 AWG NM-B (55 A ÷ 1.25) even if a 60 A breaker is used.

How Far Can You Run 6 AWG Wire?

Longest one-way run for copper at 3% voltage drop, single-phase: Lmax = 0.03 × V × 1000 / (2 × I × R), with R = 0.491 Ω/1000 ft (NEC Chapter 9 Table 8, uncoated copper at 75 °C). This is a resistance-only estimate; reactance and power factor are not modeled, and 3% is a design target, not a code limit. Each distance opens the calculator with that load (non-continuous, copper, 75 °C terminals).

Load120 V240 V
40 A91 ft183 ft
50 A73 ft146 ft
55 A66 ft133 ft
60 A61 ft122 ft

Example: a 50 A load at 240 V, 100 ft away. 8 AWG carries 50 A but drops more than 3% at that distance, so the calculator picks 6 AWG (2.05% drop). Open this example

6 AWG Ampacity After Derating

THHN/THWN-2 is derated from its 90 °C value (NEC 310.15(B)(1) ambient, 310.15(C)(1) bundling), and the result still cannot exceed the 75 °C terminal rating of 65 A. Ambient means the temperature around the conductor where it runs. Click a row to open it in the ampacity calculator.

6 AWG Diameter and Cross-Section

Bare diameter, solid (AWG definition)0.162 in / 4.12 mm
Bare diameter, 7-strand (NEC Ch. 9 Table 8)0.184 in / 4.67 mm
Metal cross-section26,240 circular mils / 13.3 mm²

Insulated outside diameter depends on the insulation type and manufacturer; check the cable spec sheet for conduit fill. Values computed on November 1, 2026 from this site's NEC 2023 tables.

6 AWG Wire FAQ

How many amps can 6 AWG wire carry?

6 AWG copper is rated 55/65/75 A at 60/75/90 °C and aluminum 40/50/55 A (NEC Table 310.16). With 75 °C terminals that is 65 A copper (60 A breaker) or 50 A aluminum (50 A breaker).

Can 6 AWG copper wire handle 60 amps?

A 6 AWG THHN/THWN-2 copper circuit in conduit with 75 °C terminals can be protected at 60 A, because the conductor is rated 65 A. If the load is continuous (3 hours or more), a 60 A circuit may carry only 48 A. 6 AWG NM-B (Romex) is limited to the 60 °C column, 55 A.

How many amps can 6 AWG wire carry at 240 volts?

The same as at 120 V: ampacity depends on the conductor and insulation, not the voltage. Voltage changes how far you can run it: a 50 A load stays within 3% drop up to about 146 ft at 240 V, but only 73 ft at 120 V (copper, resistance-only estimate).

Is 6 AWG wire good for a 50 amp circuit?

Yes. 6 AWG copper is rated at least 55 A in every 310.16 column, so it is the usual choice for a 50 A range, EV charger or sub-panel when the run is long or the cable is NM-B (8 AWG NM-B is only 40 A). A 50 A EV circuit supplies a charger set to 40 A continuous.

Common Uses for 6 AWG Wire

  • 55–65A circuits — 50A spas, 60A sub-panels, large EV
  • Detached garage and shop feeders
Ampacities are from NEC Table 310.16. Copper 14, 12 and 10 AWG are limited to 15A, 20A and 30A overcurrent protection, aluminum 12 and 10 AWG to 15A and 25A (240.4(D)). Terminations rated 60°C or 75°C usually cap the usable ampacity below the 90°C value.

Calculate wire size for your load and distance

Use the calculator to size wire for your current, distance and voltage.

Open calculator

Related Wire Gauges