What Size Wire for a NEMA 14-50 Outlet?
Wire and breaker sizing for a NEMA 14-50 Outlet — the typical 240V circuit, plus the code details (NEC 210.8) that change the answer.
Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated June 2026.
On a 50A 240V circuit (NEMA 14-50) at 75°C terminations. 60°C terminations: 6.
Protected by a 50A breaker (NEC 240.6).
GFCI required. The 2023 NEC (210.8(D) for specific appliances, 210.8(A) for kitchen/outdoor receptacles) requires GFCI protection here. Verify the code edition your jurisdiction has adopted.
NEMA 14-50 Outlet Circuit Details
- A NEMA 14-50 is a 50A, 240V receptacle used for EV charging, ranges and RVs.
- A 50A circuit needs 8 AWG copper minimum at 75°C terminations; many installers run 6 AWG for voltage-drop headroom or 60°C-rated terminations.
- NEC 210.8 requires GFCI protection for 14-50 receptacles in dwellings.
Long run to your nema 14-50 outlet?
Over distance, voltage drop can require a larger wire than the table above. See the 50A wire size by distance:
Size it for your exact install
Open the calculator pre-filled with 50A at 240V to add distance, material and temperature.