What Size Wire for an Electric Range?
Wire and breaker sizing for an Electric Range — the typical 240V circuit, plus the code details (NEC 310.16) that change the answer.
Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated June 2026.
On a 50A 240V circuit (NEMA 14-50) at 75°C terminations. 60°C terminations: 6.
Protected by a 50A breaker (NEC 240.6).
Electric Range current varies by model. The size above is the common case — always size the conductor to the unit’s nameplate rating and protect it at the labeled maximum breaker/fuse.
GFCI required. The 2023 NEC (210.8(D) for specific appliances, 210.8(A) for kitchen/outdoor receptacles) requires GFCI protection here. Verify the code edition your jurisdiction has adopted.
Electric Range Circuit Details
- Size to the range nameplate. Ranges rated 8¾ kW and up typically use a 50A circuit (8 AWG copper at 75°C; 6 AWG for 60°C terminations or margin); smaller ranges can use 40A (8 AWG).
- NEC 210.19(A)(3) allows the branch circuit to be sized to the demand, not the nameplate sum.
- Modern installs require a 4-wire NEMA 14-50.
Long run to your electric range?
Over distance, voltage drop can require a larger wire than the table above. See the 50A wire size by distance:
Size it for your exact install
Open the calculator pre-filled with 50A at 240V to add distance, material and temperature.