What Size Wire for 200 Amps at 200 Feet?

Voltage-drop-aware wire sizing for a 200-amp circuit running 200 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated June 2026.

Copper · ≤3% drop
3/0

Actual drop 2.6%. For ≤5% drop: 3/0 (2.6%).

Aluminum · ≤3% drop
250 kcmil

Actual drop 2.8%. For ≤5% drop: 250 kcmil (2.8%).

At 200 ft, ampacity still governs: 3/0 AWG copper carries 200A and its drop (2.6%) is already within 3% — no upsizing needed.

Voltage Drop at 200 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 200 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
3/02.6%4.2%
4/02.0%3.3%
250 kcmil1.7%2.8%
300 kcmil1.4%2.4%
350 kcmil1.2%2.0%
400 kcmil1.1%1.8%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 200A, 240V, 200 ft to adjust material, temperature and drop target.

Open calculator

200 Amps at Other Distances