What Size Wire for 200 Amps at 150 Feet?

Voltage-drop-aware wire sizing for a 200-amp circuit running 150 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
3/0

Actual drop 1.9%. For ≤5% drop: 3/0 (1.9%).

Aluminum · ≤3% drop
250 kcmil

Actual drop 2.1%. For ≤5% drop: 250 kcmil (2.1%).

At 150 ft, ampacity still governs: 3/0 AWG copper carries 200A and its drop (1.9%) is already within 3% — no upsizing needed.

Voltage Drop at 150 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 150 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
3/01.9%3.1%
4/01.5%2.5%
250 kcmil1.3%2.1%
300 kcmil1.1%1.8%
350 kcmil0.9%1.5%
400 kcmil0.8%1.3%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 200A, 240V, 150 ft to adjust material, temperature and drop target.