What Size Wire for 15 Amps at 75 Feet?

Voltage-drop-aware wire sizing for a 15-amp circuit running 75 ft (one-way) at 120V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
10

Actual drop 2.3%. For ≤5% drop: 12 (3.6%).

Aluminum · ≤3% drop
8

Actual drop 2.4%. For ≤5% drop: 10 (3.8%).

At 75 ft, voltage drop governs: ampacity alone would allow 14 AWG copper, but staying ≤3% requires upsizing to 10.

Voltage Drop at 75 Feet

Voltage drop is calculated for a 120V single-phase circuit over a 75 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
145.8%9.5%
123.6%6.0%
102.3%3.8%
81.4%2.4%
60.9%1.5%
40.6%1.0%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 15A, 120V, 75 ft to adjust material, temperature and drop target.

Open calculator

15 Amps at Other Distances