What Size Wire for 15 Amps at 25 Feet?

Voltage-drop-aware wire sizing for a 15-amp circuit running 25 ft (one-way) at 120V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
14

Actual drop 1.9%. For ≤5% drop: 14 (1.9%).

Aluminum · ≤3% drop
12

Actual drop 2.0%. For ≤5% drop: 12 (2.0%).

At 25 ft, ampacity still governs: 14 AWG copper carries 15A and its drop (1.9%) is already within 3% — no upsizing needed.

Voltage Drop at 25 Feet

Voltage drop is calculated for a 120V single-phase circuit over a 25 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
141.9%3.2%
121.2%2.0%
100.8%1.3%
80.5%0.8%
60.3%0.5%
40.2%0.3%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 15A, 120V, 25 ft to adjust material, temperature and drop target.

Open calculator