What Size Wire for 125 Amps at 250 Feet?

Voltage-drop-aware wire sizing for a 125-amp circuit running 250 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
2/0

Actual drop 2.5%. For ≤5% drop: 1 (4.0%).

Aluminum · ≤3% drop
4/0

Actual drop 2.6%. For ≤5% drop: 2/0 (4.1%).

At 250 ft, voltage drop governs: ampacity alone would allow 1 AWG copper, but staying ≤3% requires upsizing to 2/0.

Voltage Drop at 250 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 250 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
14.0%6.6%
1/03.2%5.2%
2/02.5%4.1%
3/02.0%3.3%
4/01.6%2.6%
250 kcmil1.3%2.2%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 125A, 240V, 250 ft to adjust material, temperature and drop target.

Open calculator