24V 30A DC Wire Size at 10 Feet
Low-voltage DC wire sizing for solar, RV, marine and battery circuits — where voltage drop, not ampacity, almost always sets the wire size.
Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated June 2026.
Actual drop 1.9% at 10 ft.
Drop 1.9%. Suggested fuse/breaker: 40A.
Drop is calculated for the full round trip (10 ft each way). At 24V even a small voltage loss is a large percentage, so this size carries the 40 A fuse rating (75°C copper) and also meets the drop limit.
Solar (NEC 690.8): PV source/output circuits base maximum current on the module short-circuit current (commonly 125% of Isc), and conductor/OCPD sizing can effectively reach 156% where a second 125% continuous factor applies. Battery, inverter and load circuits are sized differently. The 40A fuse shown is only a starting point — confirm against the module max-series-fuse, charge controller and inverter ratings.
Voltage Drop by Wire Size (24V, 30A, 10 ft)
| Wire size | Voltage drop | Within 3%? |
|---|---|---|
| 8 | 1.9% | |
| 6 | 1.2% | |
| 4 | 0.8% | |
| 3 | 0.6% | |
| 2 | 0.5% | |
| 1 | 0.4% |
Copper, DC resistance (NEC Chapter 9, Table 8). Aluminum is rarely used for low-voltage DC. Always also verify conductor ampacity and the manufacturer’s fuse/breaker requirement.
Common 24V DC Uses
- 24V solar arrays
- Larger RV/marine battery banks
- Off-grid inverter feeds
- Telecom/industrial DC
Different current or run?
Open the calculator in DC mode pre-filled with 24V, 30A, 10 ft.