12V 60A DC Wire Size at 30 Feet
Low-voltage DC wire sizing for solar, RV, marine and battery circuits — where voltage drop, not ampacity, almost always sets the wire size.
Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated June 2026.
Actual drop 2.9% at 30 ft.
Drop 1.8%. Suggested fuse/breaker: 80A.
Drop is calculated for the full round trip (30 ft each way). At 12V even a small voltage loss is a large percentage, so voltage drop governs — the wire is larger than the 4 AWG needed to carry the 80 A fuse (75°C copper).
Solar (NEC 690.8): PV source/output circuits base maximum current on the module short-circuit current (commonly 125% of Isc), and conductor/OCPD sizing can effectively reach 156% where a second 125% continuous factor applies. Battery, inverter and load circuits are sized differently. The 80A fuse shown is only a starting point — confirm against the module max-series-fuse, charge controller and inverter ratings.
Voltage Drop by Wire Size (12V, 60A, 30 ft)
| Wire size | Voltage drop | Within 3%? |
|---|---|---|
| 4 | 9.2% | — |
| 3 | 7.3% | — |
| 2 | 5.8% | — |
| 1 | 4.6% | — |
| 1/0 | 3.7% | — |
| 2/0 | 2.9% |
Copper, DC resistance (NEC Chapter 9, Table 8). Aluminum is rarely used for low-voltage DC. Always also verify conductor ampacity and the manufacturer’s fuse/breaker requirement.
Common 12V DC Uses
- RV and camper 12V systems
- Car/marine accessories
- Solar to charge controller
- Trolling motors and winches
Different current or run?
Open the calculator in DC mode pre-filled with 12V, 60A, 30 ft.