What Size Wire for 50 Amps at 75 Feet?

Voltage-drop-aware wire sizing for a 50-amp circuit running 75 ft (one-way) at 240V — because over distance, voltage drop, not ampacity, often sets the wire size.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper · ≤3% drop
8

Actual drop 2.4%. For ≤5% drop: 8 (2.4%).

Aluminum · ≤3% drop
6

Actual drop 2.5%. For ≤5% drop: 6 (2.5%).

At 75 ft, ampacity still governs: 8 AWG copper carries 50A and its drop (2.4%) is already within 3% — no upsizing needed.

Voltage Drop at 75 Feet

Voltage drop is calculated for a 240V single-phase circuit over a 75 ft one-way run (conductor length doubled for the return). Sizes meeting the ≤3% target are highlighted.

Wire sizeCopper dropAluminum dropWithin 3%?
82.4%3.9%
61.5%2.5%
41.0%1.6%
30.8%1.3%
20.6%1.0%
10.5%0.8%

Drop % uses NEC Chapter 9, Table 8 DC resistance — an accepted approximation for typical power-factor AC branch circuits. The wire must also meet ampacity; both checks are applied above.

Different distance or voltage?

Open the calculator pre-filled with 50A, 240V, 75 ft to adjust material, temperature and drop target.

Open calculator