600 kcmil Wire Ampacity & Specifications

NEC ampacity, resistance and typical uses for 600 kcmil copper and aluminum wire.

Calculations are built on the 2023 National Electrical Code (NEC) and cross-checked against the published code tables. How we verify. Last reviewed June 2026.

Copper 75°C
420A
Copper 90°C
475A
Aluminum 75°C
340A
Typical breaker
400A

600 kcmil Wire Specifications

Ampacity — Copper (60 / 75 / 90°C)350 / 420 / 475 A
Ampacity — Aluminum (60 / 75 / 90°C)285 / 340 / 385 A
Cross-section600,000 circular mils
DC resistance — Copper0.0214 Ω / 1000 ft
DC resistance — Aluminum0.0353 Ω / 1000 ft
Typical voltage drop (240V)0.4% at 50 ft · 0.7% at 100 ft (at 400A)

Common Uses for 600 kcmil Wire

  • 420A copper feeders
  • Service entrances (often paralleled)
Ampacities are from NEC Table 310.16. 14, 12 and 10 AWG are limited to 15A, 20A and 30A overcurrent protection (240.4(D)). Terminations rated 60°C or 75°C usually cap the usable ampacity below the 90°C value.