48V 50A DC Wire Size at 10 Feet

Low-voltage DC wire sizing for solar, RV, marine and battery circuits — where voltage drop, not ampacity, almost always sets the wire size.

Ampacity figures are taken from 2023 NEC Table 310.16, and automated tests check selected values against that table. Not reviewed by a licensed electrician; confirm with your local inspector. How we verify. Last updated June 2026.

Copper · ≤3% drop
4 AWG

Actual drop 0.6% at 10 ft.

Copper · ≤2% drop (solar)
4 AWG

Drop 0.6%. Suggested fuse/breaker: 70A.

Drop is calculated for the full round trip (10 ft each way). At 48V even a small voltage loss is a large percentage, so this size carries the 70 A fuse rating (75°C copper) and also meets the drop limit.

Solar (NEC 690.8): PV source/output circuits base maximum current on the module short-circuit current (commonly 125% of Isc), and conductor/OCPD sizing can effectively reach 156% where a second 125% continuous factor applies. Battery, inverter and load circuits are sized differently. The 70A fuse shown is only a starting point — confirm against the module max-series-fuse, charge controller and inverter ratings.

DC safety: The fuse protects the wire — place it close to the battery/source, and never let the OCPD exceed the conductor’s ampacity, the equipment’s max fuse rating, or the PV module’s max-series-fuse. Use DC-rated breakers/fuses with an adequate interrupt rating (battery fault current can be enormous). Voltage-drop sizing does not replace ampacity, terminal/insulation temperature, bundling or ambient derating.

Voltage Drop by Wire Size (48V, 50A, 10 ft)

Wire sizeVoltage dropWithin 3%?
40.6%
30.5%
20.4%
10.3%
1/00.3%
2/00.2%

Copper, DC resistance (NEC Chapter 9, Table 8). Aluminum is rarely used for low-voltage DC. Always also verify conductor ampacity and the manufacturer’s fuse/breaker requirement.

Common 48V DC Uses

  • 48V solar and battery banks
  • Off-grid home power walls
  • Golf cart / EV battery packs
  • Server/telecom DC plant

Different current or run?

Open the calculator in DC mode pre-filled with 48V, 50A, 10 ft.