Wire Size Calculator

Professional electrical wire sizing tool based on National Electrical Code (NEC) standards. Calculate proper wire gauge, voltage drop, and ampacity for safe electrical installations.

NEC 2023 Compliant
Used by 50,000+ Professionals
100% Free Tool

Professional Wire Size Calculator

Calculate proper wire gauge based on NEC standards. Input your electrical parameters to get accurate wire size recommendations for safe installations.

Circuit Parameters

Quick Presets

Calculation Results

Why Wire Size Matters: Safety and Efficiency

Selecting the correct wire size is crucial for electrical safety, code compliance, and system efficiency. Undersized wires can cause dangerous overheating, voltage drops, and fire hazards.

How to Use This Wire Size Calculator

Our professional wire size calculator follows NEC standards to determine the minimum safe wire gauge for your electrical installation. Here's how to use it effectively:

  1. Enter the load current - This is the maximum amperage your circuit will carry
  2. Select system voltage - Common values are 120V, 240V, 480V, or DC voltages
  3. Input cable distance - One-way length from panel to load
  4. Choose voltage drop limit - 3% for branch circuits, 2% for sensitive equipment
  5. Select wire material - Copper is recommended for most applications
  6. Pick installation method - Affects ampacity due to heat dissipation

Understanding Inputs: Amps, Voltage, Distance, and Voltage Drop

Each input parameter plays a critical role in wire sizing calculations. For common questions about these parameters, visit our FAQ section:

Current (Amperage): The electrical load determines minimum wire ampacity requirements. Always use the full-load amperage, not the breaker size.
Voltage: System voltage affects voltage drop calculations. Higher voltages allow smaller wires for the same power.
Distance: Longer cable runs increase resistance and voltage drop. The calculator uses one-way distance and automatically accounts for the return path.
Voltage Drop: NEC recommends maximum 3% voltage drop for branch circuits and 5% for feeders. Lower percentages ensure better performance.

Explanation of Wire Gauge (AWG) and Types

The American Wire Gauge (AWG) system is the standard method for sizing electrical conductors in North America. Understanding AWG numbers is essential for proper wire selection - remember that smaller AWG numbers indicate larger wire diameters.

Common Household Circuits

  • 14 AWG: 15A lighting circuits
  • 12 AWG: 20A outlet circuits
  • 10 AWG: 30A appliance circuits
  • 8 AWG: 40A electric ranges

Heavy-Duty Applications

  • 6 AWG: 50A electric dryers
  • 4 AWG: 70A electric water heaters
  • 2 AWG: 100A sub-panels
  • 1/0 AWG: 150A main feeders

Wire Types (Insulation)

  • THWN: Wet locations, conduit
  • THHN: Dry locations, higher temp
  • NM-B: Residential cable (Romex)
  • UF-B: Underground feeder

Pro Tip: Wire Material Selection

While aluminum wire is less expensive and lighter than copper, it requires special considerations. For DC circuits like solar systems, see our DC wiring guide:

Copper Advantages:
  • Higher ampacity per size
  • Better corrosion resistance
  • Standard terminations
  • More flexible installation
Aluminum Considerations:
  • Requires CO/ALR rated devices
  • Special anti-oxidant compounds
  • Proper torque specifications
  • Larger size for same ampacity

National Electrical Code (NEC) Guidelines and Tables

The National Electrical Code provides comprehensive tables and requirements for conductor sizing. Our calculator incorporates key NEC provisions to ensure safe and compliant installations. For detailed information, visit our comprehensive NEC Article 310 guide:

Key NEC Articles for Wire Sizing:

Article 310: Conductors for General Wiring - Contains ampacity tables for different installation methods and temperatures
Article 210: Branch Circuits - Specifies voltage drop recommendations and circuit protection requirements
Article 215: Feeders - Covers feeder conductor sizing and voltage drop calculations
Article 690: Solar Photovoltaic Systems - Special requirements for DC circuits and derating factors

NEC Table 310.16 Highlights:

AWGCopper 75°CAluminum 75°C
1420A-
1225A20A
1035A30A
850A40A
665A50A

*Ampacities for conductors in conduit/raceway (3 or fewer current-carrying conductors)

How to Calculate Voltage Drop and Why It's Critical

Voltage drop occurs when electrical current flows through wire resistance, reducing the voltage available at the load. Excessive voltage drop can cause equipment malfunction, reduced efficiency, and potential safety hazards.

The Voltage Drop Formula

Single Phase AC / DC:
VD = (2 × I × R × L) / 1000
Where: VD = Voltage Drop (V), I = Current (A), R = Resistance (Ω/1000ft), L = Length (ft)
Three Phase:
VD = (1.732 × I × R × L) / 1000

Consequences of High Voltage Drop

  • • Motors run hot and inefficiently
  • • Lights dim and flicker
  • • Equipment may not start properly
  • • Increased energy consumption
  • • Potential fire hazards

NEC Voltage Drop Recommendations

  • Branch Circuits: 3% maximum
  • Feeders: 5% maximum
  • Combined: 5% total maximum
  • Sensitive Equipment: 2% or less
  • Motor Circuits: Consider starting current

Solutions for Long Runs

  • • Increase wire size (most common)
  • • Use higher system voltage
  • • Install intermediate distribution
  • • Consider voltage regulators
  • • Parallel conductor runs

Choosing the Right Conduit and Breaker Size

Proper conduit sizing and circuit protection are essential components of a safe electrical installation. These elements work together with wire sizing to create a complete, code-compliant system. Learn more in our conduit sizing guide.

Conduit Fill Requirements

NEC Article 314 limits the number of conductors in conduit to prevent overheating and facilitate wire pulling:

Conduit Size14 AWG12 AWG10 AWG
1/2"975
3/4"16139
1"262215

Circuit Breaker Sizing Rules

General Rule: Breaker size should not exceed wire ampacity (with exceptions for motor circuits)
Standard Sizes: 15A, 20A, 30A, 40A, 50A, 60A, 70A, 80A, 90A, 100A
80% Rule: Continuous loads should not exceed 80% of breaker rating
Motor Protection: May require separate overload protection

Crucial Safety Warnings and Common Installation Mistakes

Electrical work can be dangerous. Understanding these critical safety points and avoiding common mistakes can prevent fires, injuries, and code violations. For more questions, check our comprehensive FAQ.

⚠️ Critical Safety Warnings

Electrical Permits and Inspections

Most electrical work requires permits and inspections. Check with your local authority having jurisdiction (AHJ) before beginning work. Unpermitted work can void insurance and create safety hazards.

Turn Off Power and Verify

Always turn off power at the breaker and use a non-contact voltage tester to verify the circuit is de-energized before working. Test your tester on a known live circuit first to ensure it's working properly.

Ground Fault Protection

Install GFCI protection for circuits in wet locations (bathrooms, kitchens, outdoors, basements). AFCI protection is required for most 15A and 20A branch circuits in dwelling units.

Professional Installation Required

Complex installations, service upgrades, and work involving main panels should only be performed by licensed electricians. When in doubt, consult a professional - it's worth the cost for safety and code compliance.

🔧 Common Installation Mistakes to Avoid

Undersized Neutral Conductors

The neutral conductor must be sized the same as the hot conductors for most circuits. Never assume the neutral carries less current - it carries the unbalanced current and must handle full load.

Ignoring Temperature Derating

Wire ampacity must be derated for high ambient temperatures and conduit fill. Attics, outdoor installations, and conduits with multiple circuits require careful ampacity calculations.

Improper Aluminum Wire Connections

Aluminum wire requires CO/ALR rated devices and special anti-oxidant compounds. Improper connections can cause arcing, overheating, and fires. Follow manufacturer instructions exactly.

Mixing Wire Gauges in Same Circuit

All conductors in a circuit must be sized for the overcurrent protection device rating. You can't splice smaller wire onto larger wire to "save money" - the smallest conductor determines the circuit rating.

Inadequate Working Space

NEC Article 110.26 requires specific working clearances around electrical equipment. Minimum 3 feet of clear space in front of panels, and adequate headroom for safe operation.

🎓 Final Professional Recommendations

Before You Start:

  • • Research local electrical codes and requirements
  • • Obtain necessary permits and schedule inspections
  • • Use quality materials rated for the application
  • • Plan your installation route and access
  • • Have proper tools and safety equipment

When to Call a Professional:

  • • Service panel modifications or upgrades
  • • Complex three-phase installations
  • • Underground or overhead service connections
  • • Commercial or industrial applications
  • • Any work you're not completely confident about

Remember: This calculator provides theoretical calculations for reference only. Always consult local codes and licensed professionals for actual installations. Your safety and code compliance are worth the investment in professional expertise.